INSTALLATION
Wall Mounted 0121…0661
Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0. - Date: 15-05-2000 EN
19 (22)
RECOMMENDED POWER SUPPLY CABLE SECTIONS AND LINE FUSES
Power cable is not supplied by UNIFLAIR ITALIA Srl and must be appropriately dimensioned by the installer. For
short distances (
< 30 m ) the recommended sections are shown in the table below:
MAIN 230V/1N/50Hz LINE UPS 230V/1N/50Hz LINE (opt.)
MODEL LINE FUSE (a) MODEL LINE
WM* 0121
2x4+4PE 40A
WM* 0121
2x1.5
WM* 0181
2x4+4PE 40A
WM* 0181
2x1.5
WM* 0251
2x4+4PE 40A
WM* 0251
2x1.5
WM* 0281
2x4+4PE 40A
WM* 0281
2x1.5
MAIN 400V/3N/50Hz LINE UPS 230V/1N/50Hz LINE (opt.)
MODEL LINE FUSE (a) MODEL LINE
WM* 0331
4x4+4PE 25A
WM* 0331
2x1.5
WM* 0551
4x4+4PE 40A
WM* 0551
2x1.5
WM* 0661
4x4+4PE 40A
WM* 0661
2x1.5