INSTALLATION
Wall Mounted 0121…0661
Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0. - Date: 15-05-2000 EN
15 (22)
CONNECTING THE CONDENSATE DRAIN
The condensate tray is located at the base of the evaporate coil; the condensate drains from the tray via a flexible
tube (included with the unit) behind the condensate coil.
The flexible tube has a bend which functions as a siphon and must not be removed
The flexible tube drains the condensate across the lower unit grille: it is possible to connect it to the main water
drain of the building via a plastic tube with 25mm internal diameter and a minimum slope of 1%.
REAR OF THE UNIT
Condensate coil
Condensate drain
Fig. 15.