INSTALLATION
Wall Mounted 0121…0661
18 (22)
Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0. - Date: 15-05-2000 EN
- 0551-0661 models: Locate the mains switch IG found inside the electrical circuit;
L1
L2
L3
N
PE
L10
N10
IG
IM2
IM1
O
I
UPS
(Opt.)
Fig. 17.c.
- Fix the cable terminals to the mains switch and secure the screws; connection of the yellow/green earth wire using
the terminal ‘PE’ is compulsory.
WM units can be fitted with a double power supply:
• main 400V/3N/50Hz line for:
- compressor;
- condensor fans;
- electrical heating elements;
• UPS 230V/1/50Hz line for:
-evaporator fans;
- damper motor;
- mP20 microprocessor circuit and terminal.
Units can also be specified with double power supply with emergency 48 Vcc
CONNECTING THE USER TERMINAL
- Connect the User Terminal mP20 to the Base Board found inside the electrical panel. In a few units the terminal
mP20 can be positioned beside the electrical panel (see figure18); it is fixed on a hinged bracket that allows
access to the mP20 board.
Q.E.
WM*
0121-0181
0251-0281-0331
Fig. 18.a.
Q.E.
WM* 0551-0661
Fig. 18.b.