OPERATION AND MAINTENANCE MANUAL
Wall Mounted 0121…0661
Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0. - Date: 18-07-2000 EN
21 (32)
MAINTENANCE
REGULAR CHECKS
The following maintenance operations should be done regularly:
check the set values of the control and regulation devices
check that room conditions on the mP20/W terminal display are normal
check normal condensation and evaporation pressures or saturated temperatures
check the refrigerant charge; the sight glass should be clear (however the presence of a few bubbles is normal
check the correct function of the external air damper
check normal temperature and noise levels of compressor and fans
check the air filters; clean or change the filters when the dirty filter alarm comes on
check the flow of condensate to the drain
check whether the condenser is dirty, removing any obstructing material with a jet of compressed air or water
check that all electric terminal connections are tight
check that power supply voltage is within design limits.
CLEANING AND CHANGING THE AIR FILTER
Inspect the filter cartridge at least once a
month and whenever there is a blocked filter
alarm: Clean or chage the filter as necessary.
models 0121-0331 open the central front panel
models 0551…0661 open the top front panel
- remove the filter cartridge (F), shake it to
remove large particles then clean with a
vacuum cleaner. Change the filter if it is
blocked.
F
WM 0121…0331
F
WM 0551-0661
Fig. 6.