Uniflair WMA 0281 Manual de instrucciones Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 30
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
OPERATION AND MAINTENANCE MANUAL
Wall Mounted 0121…0661
20 (32)
Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0. - Date: 18-07-2000 EN
ELECTRICAL CHARACTERISTICS
COMPONENTI DELL’UNITÁ
UNIT COMPONENTS
50 Hz
C
COMPRESSORE
COMPRESSOR
MVE
VENTILATORI sez. RICIRCOLO
RADIAL FANS
VOLT No. kW
(2)
OA
(2)
FLA LRA VOLT No. kW OA FLA LRA
WM
0121
230/1ph/50 1 0.94 4,4 8,5 32 230/1ph/50 1 0,13 0,6 0,67 1,45
WM
0181
230/1ph/50 1 1.53 7,1 11,4 47 230/1ph/50 1 0,23 1,0 1,11 2,22
WM
0251
230/1ph/50 1 1.90 9,0 13,6 61 230/1ph/50 2 0,13 0,6 0,67 1,45
WM
0281
230/1ph/50 1 2.35 11,2 15,3 76 230/1ph/50 2 0,13 0,6 0,67 1,45
WM
0331
400/3ph/50 1 2.86 5,1 6,6 46 230/1ph/50 2 0,23 1,0 1,11 2,22
WM
0551
400/3ph/50 1 4.01 7.8 10.0 66 230/1ph/50 1 0.70 3.2 3.56 7
WM
0661
400/3ph/50 1 4.88 8.6 11.4 74 230/1ph/50 1 0.70 3.2 3.56 7
MVC
VENTILATORI sez. CONDENSANTE
CONDENSER FANS
RR
RESISTENZE ELETTRICHE (opzionali)
ELECTRICAL HEATERS (optional)
VOLT No. kW
(2)
OA
(2)
FLA LRA VOLT No. kW OA
WM
0121
230/1ph/50 1 0,14 0,5 0 0 230/1ph/50 2 1,3 5,6
WM
0181
230/1ph/50 1 0,14 0,5 0 0 230/1ph/50 2 2.0 8,7
WM
0251
230/1ph/50 1 0,14 0,5 0 0 230/1ph/50 2 2.0 8,7
WM
0281
230/1ph/50 1 0,14 0,5 0 0 230/1ph/50 2 2.0 8,7
WM
0331
230/1ph/50 2 0,09 0,4 0 0 230/1ph/50 2 3.0 8.7
WM
0551
230/1ph/50 1 0.34 1.5 2,56 7 400/3ph/50 1 6.0 8.7
WM
0661
230/1ph/50 1 0.34 1.5 2,56 7 400/3ph/50 1 6.0 8.7
UNITÁ COMPLETE
COMPLETE UNITS
SENZA RESISTENZE
WITHOUT EL. HEATERS
RAFFREDDAMENTO MECCANICO
MECHANICAL COOLING
CICLO DI FREE-COOLING
FREE-COOLING CYCLE
mm² FUS VOLT kW L1 L2 L3 VOLT kW L1 L2 L3
WM
0121 C
1,5 30A 230/1ph/50 1.21 5.5 0 0 230/1ph/50 0.13 0.6 0 0
WM
0221 C
1,5 30A 230/1ph/50 1.9 8.6 0 0 230/1ph/50 0.23 1.0 0 0
WM
0251 C
2,5 40A 230/1ph/50 2.30 10.7 0 0 230/1ph/50 0.26 1.2 0 0
WM
0281 C
2,5 40A 230/1ph/50 2.75 12.9 0 0 230/1ph/50 0.26 1.2 0 0
WM
0331 C
1,5 30A 400/3ph/50+N 3.49 7.9 5,1 5,1 400/3ph/50+N 0.46 2.0 0 0
WM
0551 C
4 40A 400/3ph/50+N 5.05 12.5 7.8 7.8 400/3ph/50+N 0.70 3.2 0 0
WM
0661 C
4 40A 400/3ph/50+N 5.92 13.3 8.6 8.6 400/3ph/50+N 0.70 3.2 0 0
CON RESISTENZE
WITH EL. HEATERS
RISCALDAMENTO ELETTRICO
ELECTRICAL HEATING
DEUMIDIFIC. & POSTRISC. ELETTRICO
DEHUMIDIFICATION & ELECTRIC REHEAT
mm² FUS VOLT kW L1 L2 L3 VOLT kW L1 L2 L3
WM
0121 T
4 40A 230/1ph/50 2.73 11.8 0 0 230/1ph/50 3.81 16.7 0 0
WM
0221 T
4 40A 230/1ph/50 4.23 18.4 0 0 230/1ph/50 5.90 26.0 0 0
WM
0251 T
6 50A 230/1ph/50 4.26 18.6 0 0 230/1ph/50 6.3 28.1 0 0
WM
0281 T
6 50A 230/1ph/50 4.26 18.6 0 0 230/1ph/50 6.75 30.3 0 0
WM
0331 T
2,5 40A 400/3ph/50+N 6.46 10.7 8.7 8.7 400/3ph/50+N 9.49 16.6 13.8 13.8
WM
0551 T
4 40A 400/3ph/50+N 6.70 11.9 8.7 8.7 400/3ph/50+N 11.05 21.2 16.5 16.5
WM
0661 T
4 40A 400/3ph/50+N 6.70 11.9 8.7 8.7 400/3ph/50+N 11.92 22.0 17.3 17.3
kW kW
Potenza Nominale
(1)
Nom. Absorbed Power
(1)
OA A
Assorbimento nominale
(1)
Operating Current
(1)
FLA A
Assorbimento massimo
(1)
Full Load Current
(1)
LRA A
Corrente di spunto
(1)
Locked Rotor Current
(1)
(1)
per elemento
(1)
each Element
(2)
Ambiente: 26°C/40%UR - Test.: 35°C
(2)
Room at: 26°C / 40% - Text.: 35°C
L1-L2-L3 A Assorbimento nominale per fase
Operating Current per phase
mm² mm² Sez. cavo di alimentazione consigliata
Supply Wiring Section suggested
FUS A Fusibile di linea consigliato
Line Back-up Fuses suggested